Air Handling Unit Manufacturers
Air Handling Unit Manufacturers
  • Features
  • Technical Data
  • Application
1, Choose best materials, main components are from China top brand or imported.
 
2, The modular casing design, easy interchanging each other. easy install,easy transport,easy maintaince.
 
3, Unique no-cold-bridge design, improve the insulation and air tightness, total air leak rate ≤2.5%.
 
4, With dynamic balanced double inlet Centrifugal fan, with good air dynamic features, and accurate working, high efficiency, low vibration, low noise etc. 
 
5, High efficient heat exchanger coil, ensure to provide the enough cooling capacity to the unit. And also high efficient breakwater panel is provided if required, water flow in coil ≤3×10-4kg/kg.
 
6, Strong structure, good looking and permanent color.
 
7, Reasonable inside structure, with the suitable space for maintenance and cleaning.
 
8, Casing sheet: Provide doubleskin construction constructing Sandwich type comprising 0.5mm thick galvanized internal and external skins and with 30mm thick polystyrene insulation of minimum 45kg/m3 density. Good airproof material is use between the casing and the frame to reduce the rate of the air leak.
The combined air handling untis are modular designed ,each modular can be used independently and can also work together and company with fan coil units to add refresh air. Not only reduce operation costs and energy saving, but also optimize air quality and create a congnitive indoor space to meet the human health requirements.
GT-ZKW-()DY
Unit characteristics Model:GT-ZKW-()DY
 
40 60 80 100 130 160 180
Cooling capacity 1* kw 20.0 31.5 41.2 50.0 65.0 80.2 90.0
Heating capacity 2* kw 21.2 33.4 43.3 52.5 68.3 85.0 95.4
Air volume 3* m3/h 4000 6000 8000 10000 13000 16000 18000
Static air Pressure 3* Pa 300 300 400 500 500 500 600
Power 3N-380V-50Hz
Indoor unit Supply air fan 3* Type Efficient centrifugal fan
kw 1.5 2.2 3.0 5.5 7.5 7.5 11.0
Heater 4* Type Stainless steel tube electric heating/steam heating coil/hot water heating coil
kw 9 12 18 24 30 30 48
Section length(mm) 300 300 300 400 400 400 400
Humidifier 4* Type Steam/electrode type/Electrothermic type
Kg/h 5 8 8 12 15 15 15
Section length(mm) 400 400 400 400 400 400 400
Compressor A Type Hermetic scroll type
Qty 1 1 2 2 2 2 3
Input power kw 4.2 5.7 8.5 10 11.6 15 17.1
Compressor B Type Hermetic scroll type(Inverter system)
Qty 1 1 2 2 2 2 3
Input power kw 4.1 5.5 8.3 9.5 11.3 14.2 16.8
Refrigerant 5* Type R22/R407C/R410A
Mode External balance type thermal expansion value/Electronic expansion value
Condenser Type Plate type
Cooling water flow(m3/h) 4.1 6.4 8.1 10.3 12.9 15.8 17.6
Water pip diameter(DN) 32 32 40 50 50 65 65
Resistance loss(kPa) 15 30 25 28 35 30 35
Filter 6* Type Primary filter G4(medium effect F8/Nanocrystalline carbon filter)
Noise 7* dB(A) 65 65 66 67 68 68 70
Overall dimensions 8* Length(mm) 2800 2900 3000 3200 3400 3400 3400
Width(mm) 1030 1140 1340 1340 1650 1650 1650
Height(mm) 1115 1115 1115 1420 1420 1730 1730
Weight kg 470 800 940 1100 1200 1300 1380










Application:
The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.
 
Product Catalog