GT-ZKW-()CW
Model:GT-ZKW-()CW 300 350 400 450 500 550 600 700 800 1000
Nominal air volume m3/h 30000 35000 40000 45000 50000 55000 60000 70000 80000 100000
Static Pressure 1* Pa 600 600 600 600 600 800 800 800 800 900
Blower Power 1* Kw 18.5 18.5 22.0 22.0 30.0 30.0 37.0 37.0 45.0 55.0
Heating capacity 2* Kw 72 84 96 96 120 120 150 180 180 210
Humidifying capacity3* Kg/h 21 30 30 45 45 60 72 90 100 120
Filter 4* Type Primary effect G4(middle effect F8/Nanocrystalline carbon filter)
Power 3N-380V-50Hz
 
Cooling 4 rows return air Return air(kw)5* 179 210 245 277 306 340 375 440 504 590
Water flow(m3/h) 28.2 36.2 42.1 47.6 53.0 58.2 64.6 76.1 86.8 101.3
Water resistance(kPa) 50 20 27 29 32 35 40 25 35 48
Pipe diameter(DN) 80 65*2 65*2 80*2 80*2 80*2 80*2 100*2 100*2 100*2
4 rows fresh air All fresh air(kw)5* 310 360 410 456 510 570 600 720 840 1020
Water flow(m3/h) 55 62.5 72.2 78.4 87.6 98 103.1 123.7 144.3 175.3
Water resistance(kPa) 35 40 31 38 43 48 36 48 35 50
Pipe diameter(DN) 80*2 80*2 100*2 100*2 100*2 100*2 80*3 80*3 100*3 100*3
6 rows return air Return air(kw)5* 210 240 280 310 350 380 400 490 560 680
Water flow(m3/h) 36 42.5 48.1 52.3 60 66 68.8 84.2 96.6 116.8
Water resistance(kPa) 25 30 35 40 49 26 34 39 32 40
Pipe diameter(DN) 100 65*2 80*2 80*2 80*2 100*2 100*2 100*2 80*3 80*3
6 rows fresh air All fresh air(kw)5* 420 456 532 590 665 720 760 930 1060 1290
Water flow(m3/h) 72.5 78.4 91.4 101 114.3 123.7 130 160 182 221.6
Water resistance(kPa) 40 45 50 38 42 48 31 40 50 45
Pipe diameter(DN) 100*2 100*2 100*2 80*3 80*3 80*3 100*3 100*3 100*3 125*3
8 rows return air Return air(kw)5* 264 290 330 380 420 470 480 590 680 820
Water flow(m3/h) 44.2 49.8 56.7 65.3 72.7 80.8 82.5 101.4 116.8 141
Water resistance(kPa) 29 35 40 31 36 42 45 30 40 42
Pipe diameter(DN) 80*2 80*2 80*2 100*2 100*2 100*2 100*2 80*3 80*3 100*3
8 rows fresh air All fresh air(kw)5* 500 550 630 720 800 890 910 1120 1290 1560
Water flow(m3/h) 85 94.5 108.3 123.7 137.5 153 156.4 192.5 221.7 268
Water resistance(kPa) 40 38 46 50 38 45 35 40 45 42
Pipe diameter(DN) 100*2 80*3 80*3 80*3 100*3 100*3 100*3 125*3 125*3 100*4
 